Part Number Hot Search : 
TFS35B MY7001 PN1072 FR201 2403S MB662XXX 2MBI1 IR1205SA
Product Description
Full Text Search
 

To Download URGD Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 FRENCH CYLINDRICAL
URGD
SEMICONDUCTOR PROTECTION FUSES
PROTISTOR(R) FUSES 600V - 660V AC URGD from 63 up to 250A SIZES: 27 X 60mm
Features / Benefits Extremely high Interrupting rating Fuses: Protection of power Semiconductors according to IEC 269.1 and 4 600V-660V AC Voltage Rating aR Class according to VDE 636-23 and IEC 269.4 Model according to NF C 63210 and 63211 with built-in blown fuse indication
APPLICATIONS DATA
Voltage rating UN( VAC ) Class Current rating IN( A ) 63 80 100 125 160 200 250 pre-arcing I2t @ 1 ms I2tp (A2s) 405 860 1620 3425 6480 13700 29600 Total clearing I2t @ UN I2tt (A2s) 1840 3750 6800 13600 24600 61500 107000 Watt losses 0.8 IN 12 13.5 15 16 17 18.5 21 IN 22 24.6 27 29.5 32.5 35.7 40 Tested interrupting rating
660 V
URGD
200 kA @ 660 V
600 V
URGD
200 kA @ 600 V
Minimum operating voltage for trip-indicator: 20 V
PART NUMBERS
27x60 - With blown fuse trip-indicatior
60,3 7
TYPE
VOLTAGE
CURRENT RATING
CATALOG NO.
6.621 6.621 6.621 6.621 6.621 6.621 CP CP CP CP CP CP URGD URGD URGD URGD URGD URGD 27x60/ 63 27x60/ 80 27x60/100 27x60/125 27x60/160 27x60/200 A B C D E F
REF #
076820 076821 076822 076823 076824 076825
O 27
URGD
O5
660 V
63 80 100 125 160 200
A A A A A A
URGD
600 V
250 A
621 CP URGD 27x60/250 W 076264
D 96
FRENCH CYLINDRICAL
URGD
SEMICONDUCTOR PROTECTION FUSES
Melting Time-Current Data
D
Tolerance for the mean pre-arcing current 8% These curves indicate, for each rated current, the pre-arcing time vs. the R.M.S. pre-arcing current.
Clearing I2t vs. AC Operating Voltage
63 to 200A URGD
Peak arc Voltage
63 to 200A URGD
K 1,2 1 0,8 0,6 0,4 0,2 0 200 400 600 U(V)
250A URGD
Um(V) 2000
1000
K 1,2 1 0,8 0,6 0,4 0,2 0 100 200 300 400 500 600 U(V)
Correction factor to determine the clearing I2t of a fuse operating below its rated voltage.
0
100 200 300 400 500 600 700
250A URGD
These curves determine the peak arc voltage across the fuse terminals as a function of the applied voltage.
Um(V) 2000
1000
0
100 200 300 400 500 600 700
D 97


▲Up To Search▲   

 
Price & Availability of URGD

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X